8. The battery for backing-up the Random Access Memory (RAM) in the
recorder should be replaced every 2 to 3 years.
9. Visually inspect the perimeter of the furnace, looking for cracking in the
concrete or movement of the supporting steel structure. This should be
accomplished every three (3) months.
10. Turn off burners, one at a time, remove the flame rods and spark plugs
(igniter) and clean them using steel wool. This should be accomplished
every three (3) months or whenever a burner is difficult to light. If UV
scanners are used, they should be pulled out and the lens wiped with a
soft cloth to remove dust deposits.
11. If a standby or spare blower assembly is stored for a long period of time,
it must be carefully protected from dampness, dirt and vibration. The
inlet and discharge should be covered to keep foreign matter out. The
motor shaft should be periodically rotated a few times by hand, to keep
the shaft from warping. Failure to comply with any of the preceding will
void warranty.
12. Verify the proper settings for natural gas combustion air at both high and
low firing based on the original set up sheets. This procedure should be
done every three (3) months.
13. CAUTION: Serious burns can occur to exposed skin that is too close to
the furnace inspection ports! There will be excessive pressure and heat
surging from the port when the furnace is at high fire. Only trained
maintenance personal should perform this task. CAREFULLY open one of
the inspection doors and check for excessive amounts of back pressure
inside the combustion chamber. At high fire, you should be able to detect
pressure coming out of the port, from no more than 12” away from the
port opening, on the port opposite of the flue. If necessary, adjust waste gas
damper located in the exhaust flue stack.